Pengaruh Kualitas Air Dari Waduk Jatiluhur Sebagai Pendingin Terhadap Korosi Pada Unit Penukar Panas [Effects Of Water Quality Of Reservoir Jatiluhur As To Corrosion On Cooling Unit Heat Exchanger]

Main Article Content

Saefudin Saefudin

Abstract

The problems of corrosion and scale formation often occur in the industrial sector, especially in heat exchanger unit. The factors, which influence the corrosion of metals and scale formation are the quality of the cooling water, the temperature, pH and the kind of metals. Some of observations had been performed to analyze the influence of the cooling water from Jatiluhur Dam to corrosion at the material tube of the heat exchanger and utility which made from carbon steel type : A179C;1045; A192; and A515-70 in the variable of temperatures: 32, 37 and 50 °C, by means of the polarization method and the prediction of scale formation tendency, which determined from the chemical composition analysis of the cooling water on base of Langelier Saturation Index method. The results of observation showed that the corrosion rates of carbon steels are affected by the quality of the cooling water; the temperature, the chemicals composition. The analysis results from both samples of the cooling water have negative value of the saturation index degree. These showed that cooling water from the Jatiluhur Dam tend to a corrosive.

Article Details

How to Cite
Saefudin, S. (2015). Pengaruh Kualitas Air Dari Waduk Jatiluhur Sebagai Pendingin Terhadap Korosi Pada Unit Penukar Panas [Effects Of Water Quality Of Reservoir Jatiluhur As To Corrosion On Cooling Unit Heat Exchanger]. Jurnal Metalurgi, 30(1), 7–17. https://doi.org/10.14203/metalurgi.v30i1.105
Section
Articles

References

Pierangela Cristiani. 2005.,,Solutions to fouling in power station condensers”; Applied Thermal Engineering 25, 2630–2640.

Nagaraj Tumma, 2013. ,,Heat Exchanger Fundamentals”. Chevron Oronite Pte Ltd 22nd.

General electric, 2013 “Water Industries Ltd.“ Hand Book Water Treatment “.

Konstantinos D. Demadis. 2003.,,Combating Heat Exchanger Foulingand Corrosion Phenomena in ProcessWaters”, Compact Heat Exchangersand Enhancement Technology for the Process Industries. R.K. Shah, Ed., Begell House Inc., 483-491.

Bennett P. Boffardi, Calgon Corporation. 2006.,,Control of Environmental Variables in Water Recirculating System”, Metal Handbook Ninth Edition, Volume 13 Corrosion, p 487-497.

Russel W. Lane.1993.,,Control of Scale and Corosion in Building Water System”, Mc. Graw-Hill, Inc.

S. Sastri, E. Ghali, and M. Elboujdaini. 2007. ,,Corrosion Prevention and Protection, Practical Solutions”, Wiley, Chichester, England.

R. Winston Revie and Herbert H. Uhlig Corrosion and Corrosion Control, by Copyright © 2008 John Wiley & Sons, Inc.

ASTM G5‐94 e1: Standard Reference Test Method for Making Potentiostatic and Potentiodynamic Anode Polarization Measurements, 2011.

HM Revenue and Customs.,“Clasification iron and steel”, 3 june 2013.

JIS Hand Book Ferrous Materials and Metallurgy; JIS G 0552 : Methode of Ferrite Grain Size Test for Steel; 1979.